Power system resonance occurs in cases of strong non-linearity. This paper uses the simplest normal form theory to derive the simplest normal form of a power system at the second-order resonance point. This approach is able to solve the problem that traditional normal form coefficients at the second-order resonance point are strange. By calculating the approximate analytical solutions,participation factors can be fixed,the changing process of the dominant stability mode can be analyzed;then the physical mechanism caused by the second-order resonance point dominant stable mode can be revealed. The simulation results indicate that the second-order resonance close to the saddle-node bifurcation is the critical region which forms the voltage stability dominant mode. This change is caused by the resonance terms. The proposed method is useful for a profound understanding of the relationship between voltage stability and angle stability.
Time-Frequency Domain Dissipation Energy Flow Method for Forced Oscillation Source Location in Power System
单机等值系统调速器死区对频率振荡的影响
Related Author
ZHANG Tian
YAO Jun
YANG Dong
JIN Rongyu
ZHAO Linsheng
XIE Hai
JIANG Tao
YE Nan
Related Institution
State Key Laboratory of Power Transmission Equipment Technology (Chongqing University)
Key Laboratory of Modern Power System Simulation and Control & Renewable Energy Technology, Ministry of Education (Northeast Electric Power University)
State Key Laboratory of Power Grid Safety and Energy Conservation(China Electric Power Research Institute)
College of Electrical Engineering, Zhejiang University
Department of Electrical Engineering, Tsinghua University