Special Problems in Pilot Protections of TransmissionLines Connecting Wind Farms
|更新时间:2025-08-13
|
Special Problems in Pilot Protections of TransmissionLines Connecting Wind Farms
Automation of Electric Power SystemsVol. 36, Issue 8, Pages: 143-147(2012)
作者机构:
Key Laboratory of Smart Grid of Ministry of Education,Tianjin University,Tianjin,China,300072
作者简介:
基金信息:
DOI:
CLC:
Published:2012
稿件说明:
移动端阅览
Bin LI, Meng LIN, Xulu FAN, et al. [J]. Automation of electric power systems, 2012, 36(8): 143-147.
DOI:
Bin LI, Meng LIN, Xulu FAN, et al. [J]. Automation of electric power systems, 2012, 36(8): 143-147.DOI:
Special Problems in Pilot Protections of TransmissionLines Connecting Wind Farms
摘要
As the penetration of wind power into power grids increases,higher demands are made on the stability andprotection of power systems.Unlike traditional synchronous generators,wind turbines are different on the short-circuit and impedance characteristics,thus some problems exist in pilot protections of transmission linesconnecting wind farms.When a single-phase fault occurs on a transmission line,the phase selector based on current-difference sudden-change may mistake the single-phase fault for a phase-to-phase fault.This paper studiesthe impedance characteristics of an asynchronous wind generator,and analyzes the behavior of a fault phase selectorunder different conditions.Then,the paper explains that inequality between positive and negative branch coefficientsis the cause for the mal-operation of the fault phase selector.Finally,some simulations are done in MATLAB tovalidate analysis results.
Abstract
As the penetration of wind power into power grids increases,higher demands are made on the stability andprotection of power systems.Unlike traditional synchronous generators,wind turbines are different on the short-circuit and impedance characteristics,thus some problems exist in pilot protections of transmission linesconnecting wind farms.When a single-phase fault occurs on a transmission line,the phase selector based on current-difference sudden-change may mistake the single-phase fault for a phase-to-phase fault.This paper studiesthe impedance characteristics of an asynchronous wind generator,and analyzes the behavior of a fault phase selectorunder different conditions.Then,the paper explains that inequality between positive and negative branch coefficientsis the cause for the mal-operation of the fault phase selector.Finally,some simulations are done in MATLAB tovalidate analysis results.