A complicated DC line fault of high voltage direct current(HVDC) is analyzed. During this DC line fault, the continuous lightning strikes resulted to action of several protections such as: DC line over-voltage protection, valve group differential protection, AC/DC conductor contact protection, bridge differential protection and 50 Hz protection, etc. In accordance with protection function principle of DC control concerned and fault records, a detailed analysis on the fault process is carried out. Furthermore, the improving suggestions such as: study on reason and influence of DC line over-voltage, attach importance to the coordination of thyristor valve and its control system with the DC protection, properly improve the logic of the open HSNBS, etc are put forward.