To analyse the impacts of the overvoltage of energizing no-load cable to a microgrid, the simulation model of the microgrid based on PSCAD/EMTDC is designed. This simulation model includes three types of micro-sources, small synchronous generators, wind turbine generators based on asynchronous generators and micro-sources based on inverters. This paper studies the overvoltage level under three kinds of conditions, different cable length, different micro-source types and different system operation models. The results shows that the overvoltage of energizing no-load cable exceeds 4 p.u. when the cable length is less than 1 km, which endangers the insulation of electrified equipments. In addition, the micro-source types, system parameters and operation models have certain influence on the overvoltage.
Equivalent Projection Based Cooperative Optimal Operation Method for Multi-microgrid Flexible Distribution System
Review of Stability Analysis Methods and Improvement Measures for Power System Dominated by Multiple Virtual Synchronous Generators
Related Author
FANG Yan
LI Jinghua
LAN Fei
XIE Lingling
LAI Yening
FANG Yan
LI Jinghua
LAN Fei
Related Institution
Guangxi Key Laboratory of Power System Optimization and Energy Technology (Guangxi University)
State Grid Electric Power Research Institute (NARI Group Corporation)
Key Laboratory of Guangxi Electric Power System Optimization and Energy-saving Technologys (Guangxi University)
Key Laboratory of Modern Power System Simulation and Control & Renewable Energy Technology, Ministry of Education (Northeast Electric Power University)
School of Electrical Engineering, Southeast University