Positive-sequence polarized voltage of distance relay is discussed with voltage phasor diagram method. The phase angle variation of bus voltage and bus positive-sequence voltage before and after the various asymmetrical faults for long-distance and heavy-load lines are analyzed and compared. The bus positive-sequence voltage is adopted as polarized voltage of distance relay, which can effectively reduce and avoid overreach of distance relay when the grounding fault via fault resistance occurs near the setting point of the distance relay.
Applicability Analysis of Distance Protection with Positive-sequence Voltage Polarization for Transmission Lines of Wind Farm with Direct-driven Turbines
特高压线路距离继电器静态特性分析
基于补偿电压复合极化量的自适应距离继电器
距离继电器作为变压器低压侧故障远后备保护时的性能