The current double-circuit transmission lines dynamic model developing methods and their shortcomings are analyzed. A novel principle, the minimal mutual impedance sharing principle, which can consider the mutual inductance difference between different phase-to-phase groups is proposed. Based on the parameters of actual 500 kV double-circuit transmission lines on the same tower, the feasibility and validity of the novel principle are validated.
Key Laboratory of Power System Protection and Dynamic Security Monitoring and Control Under Ministry of Education, North China Electric Power University