Based on the multiple-terminal network theory, this paper presents a method for electric parameters calculation and transient simulation analysis when a complicated fault occurs in common tower quadruple circuits. In this method, the quadruple circuits are retrieved while keeping the rest of pre-fault network unchanged. The complicated connection of the sequence network is therefore avoided. It has been applied in a PSS/E simulation program. The method is validated through its successful application in the 500 kV common tower quadruple circuits project of the East China Grid.